Technical Data of 10kV SZ9 Series Distribution Transformer | |||||||||||||||
Rated Capacity | Voltage Group(kV) | Connection Method | Loss (kW) | No-load current | Impedance Voltage | Weight (kg) | (L)(mm) | (W) | (H) | Gauge | |||||
(kVA) | HV | LV | No-load | Load | % | % | Machine | Oil | Gross | Dimension | Vertical | Horizontal | |||
200 | 0.48 | 3.06 | 1.5 | 4 | 510 | 210 | 960 | 1440 | 780 | 1140 | 550 | 520 | |||
250 | 0.56 | 3.6 | 1.4 | 600 | 230 | 1105 | 1480 | 800 | 1200 | 650 | 550 | ||||
315 | 0.67 | 4.32 | 1.4 | 690 | 260 | 1315 | 1600 | 860 | 1210 | 650 | 550 | ||||
400 | 11 | 0.8 | 5.22 | 1.3 | 890 | 310 | 1570 | 1680 | 940 | 1300 | 650 | 550 | |||
500 | 10.5 | 0.4 | 0.96 | 6.21 | 1.2 | 990 | 310 | 1710 | 1660 | 1040 | 1310 | 750 | 600 | ||
630 | 10 | 0.69 | Yyn0 | 1.2 | 7.65 | 1.1 | 4.5 | 1160 | 400 | 2050 | 1810 | 1140 | 1350 | 850 | 660 |
800 | 6.3 | 0.4 | Dyn11 | 1.4 | 9.36 | 1 | 1430 | 430 | 2480 | 1890 | 1210 | 1380 | 850 | 660 | |
1000 | 6 | 0.69 | 1.7 | 10.98 | 1 | 1530 | 540 | 2830 | 1950 | 1260 | 1510 | 850 | 660 | ||
1250 | 1.95 | 13.05 | 0.9 | 1800 | 610 | 3460 | 1960 | 1280 | 1660 | 850 | 660 | ||||
1600 | 2.4 | 15.57 | 0.8 | 2200 | 700 | 4060 | 2350 | 1620 | 2020 | 850 | 700 | ||||
2000 | 2.8 | 21.26 | 0.8 | 2460 | 800 | 4620 | 2460 | 1740 | 2050 | 820 | 820 | ||||
2500 | 3.3 | 24.69 | 0.7 | 3070 | 910 | 5630 | 2650 | 1800 | 2100 | 1070 | 1070 | ||||
(Note): (Tapping range of high voltage) ± 5%; ± 2× 2.5%, Frequency: 50Hz. |